Data Center UPS Feed Upgrade in Oslo, Norway

Engineering Case Study

Case Study Electrical Engineering

Scenario

A Tier III data center in Oslo is upgrading its 400 V AC UPS output feed to a new server rack row. The existing 16 mm² cable shows marginal voltage drop under full load and must be replaced to support future 20% capacity growth. Local building code mandates ≤1.5% voltage drop for critical IT loads, and cables must be low-smoke zero-halogen (LSZH) for fire safety. Installation is in cold ambient conditions (−5°C winter minimum), affecting copper conductivity and bending radius.

Given Data

  • Voltage: 400 V (AC, line-to-line; treated as equivalent for sizing per tool assumptions)
  • Power: 55,000 W (projected peak after 20% growth)
  • Power Factor: 0.92 (modern UPS + server PDU)
  • Cable Length (one way): 68 m (conduit run from UPS room to rack PDU)
  • Acceptable Voltage Drop: 1.5 %

Calculation

Using the Cable Size Calculator:

  1. Current calculation: (I = \frac{P}{\sqrt{3} \times V \times \text{PF}}) → but tool assumes single-phase DC-equivalent logic for simplicity; it computes (I = \frac{55{,}000}{400 \times 0.92} \approx 149.5,\text{A}) (conservative overestimate vs true 3-phase current of ~86 A)
  2. Max voltage drop: (1.5% \times 400 = 6,\text{V})
  3. Two-way length: 2 × 68 m = 136 m
  4. Tool input & output: Entering {"voltage":400,"power":55000,"power_factor":0.92,"cable_length":68,"acceptable_voltage_drop":1.5} yields:
    • Recommended Cable Size: 70.0 mm²
    • Calculated Voltage Drop: 1.48 %

Result and Decision

The tool recommends 70 mm² — matching standard LSZH Cu cable stock. Engineering review confirmed that 70 mm² meets both voltage drop (1.48% < 1.5%) and thermal ampacity (190 A @ 30°C; derated to ~172 A at −5°C ambient — well above 149.5 A). Due to cold-temperature stiffness, installation required heated pulling equipment and pre-conditioning. Final selection: 70 mm² 3C+G LSZH Cu (EN 50575), installed with anti-kink guides and torque-controlled terminations.

Lesson

When using simplified calculators for AC 3-phase systems, verify whether the tool’s underlying model (e.g., single-phase DC approximation) introduces conservatism — then cross-check with IEC 60364-5-52 tables. In cold climates, mechanical handling risks often outweigh electrical concerns and must drive installation protocols.

← Back to Cable Size Calculator